Powerware 700 VA Network Card User Manual


 
Specifications
14
Powerware
®
3110 Users Guide S Rev B www.powerware.com
Table 3. Battery
Configuration 300 VA: (1) 12V, 4.2 Ah or (2) 6V, 4.0 Ah internal battery(s)
550 VA: (1) 12V, 7.0 or 7.2 Ah internal battery
700 VA: (1) 12V, 9 Ah internal battery
Voltage 12 Vdc
Type Sealed, maintenance-free, valve-regulated, lead-acid
Charging 8 hours to 95% capacity with output fully loaded
Monitoring Advanced monitoring for earlier failure detection and warning
Backup Time 300550 VA: 3 minutes at full load; 5 minutes typical load
700 VA: 2.5 minutes at full load; 5 minutes typical load
Transfer Time 4mstypical
Table 4. Weights and Dimensions
UPS Dimensions
(HxWxD)
300 VA: 5.9 x 39.3 x 15.0 cm (2.3I x 15.5I x5.9I)
550700 VA: 7.9 x 37.6 x 17.2 cm (3.1I x 14.8I x6.8I)
UPS Weight 300 VA: 3.0 kg (6.6 lb)
550 VA: 4.2 kg (9.2 lb)
700 VA: 4.3 kg (9.4 lb)
Table 5. Environmental and Safety
120V Model 230V Model
Operating Temperature Cto40°C(32°F to 104°F)
Storage Temperature -15°Cto50°C(-5°F to 122°F)
If the UPS is stored, the batteries should be recharged every 6 months.
If stored above 25°C(77°F), battery life is reduced and should be recharged more often.
Ventilation Air around the unit must be free of dust, chemicals, or other materials
that corrode or contaminate.
Relative Humidity 5– 95% RH noncondensing
Audible Noise Online: Less than 40 dBA typical at one meter
On Battery: Less than 45 dBA typical at one meter
Surge Energy Rating 450 joules
Surge Suppression ANSI C62.41 Category A (formerly IEEE 587) IEC 61000-4-5, Level 3
Safety Conformance UL 1778; UL 497A;
CAN/CSA C22.2, No. 107.1
EN 50091-1-1 and EN 60950
Safety Markings UL, cUL NEMKO, CE
EMC (Class B) FCC Part 15, ICES-003 EN 50091-2