Powerware 9125 Power Supply User Manual


 
11
Powerware
®
9125 Two-in-One (5000/6000 VA) PDM User’s Guide S Rev B www.powerware.com
Chapter 2 Installation
This section explains:
Ī Equipment inspection
Ī PowerPass Distribution Module setup and installation
Ī Remote Emergency Power-Off (REPO) installation
Ī PDM rear panels
Inspecting the Equipment
If any equipment has been damaged during shipment, keep the shipping
cartons and packing materials for the carrier or place of purchase and
file a claim for shipping damage. If you discover damage after
acceptance, file a claim for concealed damage.
To file a claim for shipping damage or concealed d amage: 1) File with
the carrier within 15 days of receipt of the equipment; 2) Send a copy of
the damage claim within 15 days to your service representative.
NOTE Check the battery recharge date on the shipping carton label. If
the date has expired and the batteries were never recharged, do not use
the UPS. Contact your service representative.
PDM Setup
If the UPS is already installed and operating, prepare your equipment for
shutdown; then use the following procedure to shut down the UPS:
1. Turn off the equipment that is connected to the UPS.
2. Press and hold the Off button for approximately three
seconds. The UPS switches to Standby mode.
3. Unplug the UPS; the UPS shuts down in five seconds. The bar
graph and battery indicators flash briefly prior to shutdown.
4. Disconnect the power cord from the UPS input connector.
5. Disconnect the protected equipment power cord from the UPS.