Powerware FE/QFE UPS Power Supply User Manual


 
Operation
33
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
ExplanationParameter Name
(Short Form)
PasswordSample DisplayParameter
Number
3 03 --Reserved-- Reserved
4 04 I Out 3.1 Service acampsiout
(o)
The current your equipment is drawing from
the UPS.
5 05 VA Out 374 Change Not
Allowed
vaout
(va)
Volt-Amps Out. The total “apparent power”
your equipment is drawing from the UPS.
This value is based on parameter 2 multiplied
by parameter 4, and should be less than or
equal to the VA or kVA rating of the UPS. See
VA Limit, parameter 19.
6 06 I Batt 0.0 Service ibatt
(ib)
Battery Current. When the UPS is running on
AC input, this is the charging current inA.
When the UPS runs on battery power
(inverter), this is the amount of current (inA)
the batteries are supplying to the UPS.
7 07 V Batt 48.51 Service vbatt
(vb)
Battery Volts. The present battery voltage.
The UPS sounds an alarm if this value is too
low.
8 08 Freq 60.43 Hz Change Not
Allowed
frequency
(f)
In normal operation, this is the frequency of
power the UPS is receiving from the AC input
source. If this value falls outside preset
limits, the UPS goes to battery power. When
the UPS is running on battery power, this is
the frequency the UPS is supplying to your
equipment.
9 09 RunTime 12m Change Not
Allowed
runtime
(rt)
Estimated Runtime Remaining. The amount
of time the UPS continues to support your
equipment when the UPS is running on
battery power. The UPS sounds an alarm
when this value falls below a preset limit.
10 10 Date 06/01/93 None date
(d)
System Date. The UPS uses this date to
record alarms and inverter runs. The date
must be reset when you restart the UPS after
DC power is turned off.
11 or
[DISPLAY]
[1] [1] [ENTER]
11 Amb Temp 23c Change Not
Allowed
ambtemp
(at)
The temperature (in Celsius) inside the UPS.
The UPS sounds an alarm and shuts down if
this value is too high.
12 12 SinkTemp 26c Change Not
Allowed
heatsinktemp
(st)
The temperature of the heatsink. The UPS
sounds an alarm if this value is too high.
13 13 --Reserved-- Reserved