Page 33
602 Specification Table: Standard Product — FE and QFE 4.3KVA-18KVA
Model 4.3KVA/3kW 5.3KVA/3.7kW 7KVA/5kW 10KVA/7.5kW 12.5KVA/10kW 18KVA/15kW
AC Input Voltage
and Current,
Standard Charger
FE:
QFE:
100 = 38 amps
120 = 32 amps*
200 = 19 amps
208 = 18 amps
220 = 17 amps
240 = 16 amps
220 = 19 amps
230 = 18 amps
240 = 17 amps
380 = 11 amps
400 = 10 amps
415 = 9 amps
100 = 46 amps
120 = 38 amps*
200 = 23 amps
208 = 22 amps
220 = 21 amps
240 = 19 amps
220 = 21 amps
230 = 20 amps
240 = 19 amps
380 = 13 amps
400 = 12 amps
415 = 11 amps
100 = 58 amps
120 = 51 amps*
200 = 29 amps
208 = 30 amps
220 = 27 amps
240 = 26 amps
220 = 27 amps
230 = 26 amps
240 = 24 amps
380 = 16 amps
400 = 15 amps
415 = 14 amps
—
—
200 = 45 amps
208 = 45 amps
220 = 41 amps
240 = 39 amps
220 = 43 amps
230 = 41 amps
240 = 39 amps
380 = 25 amps
400 = 24 amps
415 = 23 amps
—
—
200 = 59 amps
208 = 58 amps
220 = 53 amps
240 = 50 amps
220 = 55 amps
230 = 53 amps
240 = 51 amps
380 = 33 amps
400 = 31 amps
415 = 30 amps
—
—
200 = 85 amps
208 = 86 amps
220 = 81 amps
240 = 76 amps
220 = 81 amps
230 = 78 amps
240 = 75 amps
380 = 48 amps
400 = 46 amps
415 = 44 amps
Recommended Input
Service for 60 Hz
Models**
120 = 40 amp*
208 = 25 amp
240 = 20 amp
120 = 50 amp*
208 = 30 amp
240 = 25 amp
120 = 65 amp*
208 = 40 amp
240 = 35 amp
208 = 60 amp
240 = 50 amp
208 = 75 amp
240 = 65 amp
208 = 115 amp
240 = 100 amp
Output Voltage and
Maximum Output
Current in amps***
FE:
QFE:
100 = 42 amps
120 = 34 amps
200 = 21 amps
208 = 20 amps
220 = 19 amps
240 = 17 amps
220 = 19 amps
230 = 18 amps
240 = 17 amps
100 = 52 amps
120 = 44 amps
200 = 26 amps
208 = 26 amps
220 = 24 amps
240 = 22 amps
220 = 23 amps
230 = 22 amps
240 = 21 amps
100 = 68 amps
120 = 58 amps
200 = 34 amps
208 = 34 amps
220 = 31 amps
240 = 29 amps
220 = 31 amps
230 = 30 amps
240 = 28 amps
100 = 98 amps
120 = 82 amps
200 = 49 amps
208 = 48 amps
220 = 46 amps
240 = 41 amps
220 = 45 amps
230 = 43 amps
240 = 41 amps
100 = 124 amps
120 = 103 amps
200 = 62 amps
208 = 58 amps
220 = 55 amps
240 = 51 amps
220 = 56 amps
230 = 52 amps
240 = 51 amps
100 = 176 amps
120 = 149 amps
200 = 88 amps
208 = 84 amps
220 = 82 amps
240 = 73 amps
220 = 84 amps
230 = 76 amps
240 = 73 amps
Efficiency On AC
Line
90% 90% 90% 90% 91% 92%
On Line BTU/hour:
KW/hour:
1138
.333
1403
.411
1896
.556
2844
.833
3375
.989
4452
1.3
Audible Noise (dB) 50 51 52 55 56 57
Runtime (minutes)
Full Load:
Half Load:
10
24
20
50
12
33
11
26
18
48
10
26
Weights:
Without Battery
60 Hz Units
50 Hz Units
With Battery****
60 Hz Units
50 Hz Units
N Cabinet with
Standard Batteries
243 lbs.
115.7 kgs.
348 lbs.
163.3 kgs.
—
268 lbs.
131.1 kgs.
484 lbs.
229.1 kgs.
—
362 lbs.
176.5 kgs.
578 lbs.
274.4 kgs.
—
442 lbs.
217.7 kgs.
—
—
395 lbs.
(179.2 kgs.)
505 lbs.
251.3 kgs.
—
—
535 lbs.
(242.7 kgs.)
625 lbs.
312.1 kgs.
—
—
675 lbs.
(306.2 kgs.)
Dimensions
(H x W x D)
29.5 in. x 15.5 in. x 25 in.
750 mm x 395 mm x 635 mm
NOTE:
If your model has an internal
bypass switch, add 8 in. or
200 mm to the depth.
36.5 in. x 19 in. x 32 in.
930 mm x 485 mm x 815 mm
NOTE:
If your model has an internal bypass switch, add 8 in. or 200 mm to
the depth.
* FE 4.3KVA, 5.3KVA and 7KVA models have optional 120 VAC input voltage.
** Size input protection according to all applicable local or national codes. Fuse and circuit breaker sizes vary. Sizes shown are for the U.S. and
Canada.
***At 0.7 to 0.83 leading power factor.
****FE and QFE 10KVA, 12.5KVA and 18KVA models do not have internal batteries. Batteries are in a separate battery cabinet or rack.