Rackmount Solutions VA 3000 Power Supply User Manual


 
12 Chloride Active and E-Series UPS User Manual
4.1 Commissioning of an External Battery Cabinet
The following table shows the designations of the battery cabinets which are available for the UPS devices.
Table 2. External Battery Packs
Model Cabinet Batteries
Active 700 NA NA
Active 1000 BPActive1000-19 2x (3 x 7. 2 Ah)
Active 2000 BPActive3000-19 2x (8 x 7. 2 Ah)
Active 3000 BPActive3000-19 2x (8 x 7. 2 Ah)
Disconnect the UPS from the mains and the loads from the UPS.
CAUTION: Make sure that the circuit breaker on the external battery cabinet is in the OFF position.
CAUTION: Battery cabinets are not interchangeable. Use ONLY the battery cabinet indicated above.
Connect the battery cabinet types BP1000, BP3000 to the UPS using the supplied cable. The connection
scheme is shown in the figures below. Switch the circuit breaker on the battery cabinet to the ON position.
The UPS is now ready for operation.
NOTE: Battery charging times may be longer when using an external battery cabinet.
WARNING:
Battery Plug 1
Circuit Breaker
Battery Plug 2
Fig. 13: Connection of Battery Extensions for devices Active 1000
WARNING: The connection of the external battery cabinet may only be done by qualified personnel
in accordance with the applicable safety regulations.
CAUTION: For the electrical installation, the maximum load capacity of the connection cable has to be taken into
account.