Rackmount Solutions VA 3000 Power Supply User Manual


 
Chloride Active and E-Series UPS User Manual 51
Interference immunity
IEC 801-2,level 4 / IEC 801-3,level 3
IEC 801-4,level 4 / IEC 801-5,level 2
Efficiency > 86% >90% >85%
Cooling Fan
Common Data (continued)
Noise level mains operation < 50 dBa < 55 dBa <65 dBa
Noise level battery operation < 55 dBa <65 dBa <65 dBa
Operating temperature
+ 50°F to +105°F (+10°C to + 40°C)
recommended +59°F to +89°F (+15°C to + 32°C)
Storage temperature +5°F to +104°F (-15°C to +40°C)
Relative humidity 20% to 90%, non-condensing
Altitude
max. 10,000 ft. (3,000m),
above 5,000 ft. (1,500m) max ambient temperature = 95°F
(35 °C)
Mechanical Data
UPS
Weight - lbs. 347 580 787
Dimensions - HxWxD in. (mm)
27.8 x 10.6 x 22.5
(705 x 270 x 570)
38 x 13.4 x 25
(965 x 340 x 670)
46.5 x 16.5 x 31.5
(1180 x 420 x
800)
Battery extension
Type BPE61 BPE101
Weight lbs 337 894
Dimensions - HxWxD in. (mm)
27.8 x 10.6 x 22.5
(705 x 270 x 570)
38 x 15 x 26.4
(965 x 380 x 670)
Signals
Visual LED-indication at the front side
Audible Acoustical alarm
Communications
RS232 interface
Alarm contacts +5V...+12V
Signal input +5V...+12V
ethernet
Table 12. Chloride E-Series UPS North America
UPS Model
E61XA
(E41XA*)
E101XA
(E81*)
E203XA
(E153XA*)