Rackmount Solutions VA 3000 Power Supply User Manual


 
Table 6. Active Rackmount Technical Data for North American Models
Type Active700-19 Active1000-19 Active2000-19 Active3000-19
Dimensions
Unit dimensions - WxHxD - in.
(mm)
19 x 3.5 x 17.6 19 x 3.5 x 17.6 19 x 3.5 x 18.8 19 x 3.5 x 18.8
Body dimensions - WxHxD -
in. (mm)
16.1 x 3.5 x
16.1
16.1 x 3.5 x
16.1
16.1 x 3.5 x
17.3
16.1 x 3.5 x
17.3
Weight - lbs 33 (15) 40 (18) 27 (12) 30 (13.5)
Operating Data
Ambient temperature
+50°F to 104°F (+10°C to +40°C)
5000 ft to 10000 ft: 50°F to 95°F (1500 m to 3000 m: +10°C to +35°C)
Storage temperature +5°F to +104°F (-15°C to +40°C)
Relative Humidity 20% to 90%, non-condensing
Type of cooling Fan
Safety class UL1778
RFI class FCC part 15 Class A
Efficiency > 83% > 83% > 83% > 83%
Noise level 42 dBa 42 dBa 50 dBa 50 dBa
Installation
Mains connections 5-15P 5-15P L5-20P L5-30P
Electrical load (output) (3) 5-15R (3) 5-15R (2) 5-20R (1) L5-30R
Minimum fuse protecting of
mains
10 A 15 A 20 A 30 A
Battery pack - external
BPActive1000-
19
BPActive3000-
19
BPActive3000-
19
Battery voltage 36 V 96 V 96 V
Net weight (kg) 47.5 (21.5) 59.5 (27) 59.5 (27)
Dimensions same as UPS
Chloride Active and E-Series UPS User Manual 25