3. Specifications
RuggedCom® RuggedSwitch™ 21 RS900GP Installation Guide Rev 100
3.7. Type Test Specifications
3.7.1. IEC 61850-3 Type Tests
Test Description Test Levels
Severity
Levels
Enclosure Contact +/- 8kV 4
IEC 61000-4-2 ESD
Enclosure Air +/- 15kV 4
IEC 61000-4-3 Radiated RFI Enclosure ports 20 V/m x
Signal ports +/- 2kV @ 2.5kHz x
D.C. Power ports +/- 2kV 4IEC 61000-4-4 Burst (Fast Transient)
Earth ground ports +/- 2kV 4
Signal ports
+/- 2kV line-to-earth,
+/- 1.5kV line-to-line
4
IEC 61000-4-5 Surge
D.C. Power ports
+/- 1.5kV line-to-earth,
+/- 1kV line-to-line
3
Signal ports 10V 3
D.C Power ports 10V 3IEC 61000-4-6 Induced (Conducted) RFI
Earth ground ports 10V 3
IEC 61000-4-8 Magnetic Field Enclosure ports
40 A/m continuous,
1000 A/m for 1 s
N/A
IEC 61000-4-29 Voltage Dips & Interrupts D.C. Power ports
30% for 0.1s, 60% for
0.1s, 100% for 0.05s
N/A
Signal ports
2.5kV common, 1kV
differential mode @ 1MHz
3
IEC 61000-4-12 Damped Oscillatory
D.C. Power ports
2.5kV common, 1kV
differential mode @ 1MHz
3
Signal ports 30V Continuous, 300V for 1s 4
IEC 61000-4-16 Mains Frequency Voltage
D.C. Power ports 30V Continuous, 300V for 1s 4
IEC 61000-4-17 Ripple on D.C. Power Supply D.C. Power ports 10% 3
Signal ports
1.5kV AC (Fail-
Safe Relay output)
N/A
IEC 60255-5 Dielectric Strength
D.C. Power ports 1.5kV DC N/A
Signal ports 5kV (Fail-Safe Relay output) N/A
IEC 60255-5 H.V. Impulse
D.C. Power ports 5kV N/A
Table 3.9. RS900GP IEC 61850-3 Type Tests