10.3 Modbus register map
10.3.1 Detailled status table
Status description Status to 0 Status to 1
Word
hex
Bit
0 - F
Status Familly
for
BMS design
Load powered
(protected or not protected)
No yes 40 0 Status
Load on inverter
(UPS on AC normal or on Battery and Q5N closed)
No yes 40 1 Status
UPS general alarm – UPS HMI Led Red (Nota 8) No yes 40 2 Major Fault
UPS on Battery (Nota 5) No yes 40 4 Status
Low Battery Warning (Nota 5) No yes 40 5 Major Warning
End of Battery Runtime (Nota 5) No yes 40 6 Major Fault
Load on bypass No yes 40 7 Status
Communication fault absent present 40 9 Major Fault
UPS overload No yes 40 A Major Warning
Emergency stop absent present 40 B Major Fault
Battery to be checked
or External battery monitoring fault (Nota 5)
No yes
40 D Minor Fault
Device ventilation fault (Nota 6) No yes 40 E Major Fault
41 1 Setting
41 2 Setting
UPS type (Nota 4) 0, 5, 6 : undefine,
1 : Unitary,
2 : Modulare,
3 : parallel:
4 : SSC
41 3 Setting
Manual bypass switch (Q3BP) Open Closed 41 6 Status
Rectifier major failure (Nota 5) No Yes 41 9 Major Fault
Load not protected in unitary
Load not protected in parallel (external Q5N)
No Yes 41 A Major Fault
UPS in Power Saving Mode (Nota 9) No Yes 41 B Status
UPS HMI Orange Led - (Nota 8) No Yes 41 C Major Warning
Battery present (Nota 5) absent present 42 0 Setting
Battery test in progress (Nota 5) No yes 42 8 Status
Battery over temperature (Nota 5) No fault Fault 42 A Major Fault
Battery circuit breaker (QF1) (Nota 5) Open Closed 42 F Status
AC Normal switch (Q1) Open Closed 44 3 Status
AC Normal voltage out of tolerance (Nota 5) No yes 44 8 Major Warning
Rectifier (PFC) fuse fault (Nota 5) No yes 44 9 Major Fault
AC Normal frequency out of tolerance (Nota 5) No yes 44 B Major Warning
Redundancy lost for parallel No yes 45 7 Major Warning
K2S fault (Nota 7) No yes 45 9 Minor Fault
K2S state (Nota 7) No yes 45 A Status
Overlaptransfert fault on SSC No yes 45 B Minor Warning
UPS on Maintenance position No yes 46 1 Status
AC bypass overload (Nota 7) No yes 46 5 Major Warning