Schneider Electric 66124 Network Card User Manual


 
Network Management Card & Modbus/Jbus 34022321XT indice :AE Page 79/98
Network Management Teleservice Card
APC by Schneider Electric
www.apc.com
Description of the physical quantity
Word (hex) Unit Data
type
Battery temperature (Nota 1) 14A °C unsigned
Battery charging level (Nota 1) 14B % unsigned
U AC normal (phase 1) (Nota 1) 150 V unsigned
U AC normal (phase 2) (Nota 1) 151 V unsigned
U AC normal (phase 3) (Nota 1) 152 V unsigned
Number of battery block (Nota 1) 153 - unsigned
Total battery capacity (Nota 1) 154 Ah unsigned
Nominal Apparent Power 209 kVA unsigned
Nominal battery voltage (Nota 1) 213 V unsigned
Nota1 : This Information is not present in a Static Switch Cabinet.
Nota2 : For a configuration with UPS in parallel with SCC unit, the Main 2 data need to read on the card installed in the SSC unit.
10.3.3 Environnement Sensor Table
10.3.3.1 Sensor Status table
Status description Status to 0 Status to 1 Word (hex)
Bit
0 - F
Communication fault no Yes 45 0
Alarm : temperature too high no Yes 45 1
Alarm : temperature too low no Yes 45 2
Alarm : humidity too high no Yes 45 3
Alarm : humidity too low no Yes 45 4
Input 1 alarm no Yes 45 5
Input 2 alarm no Yes 45 6
Input 1 open Closed 48 0
Input 2 open Closed 48 1
10.3.3.2 Sensor Measurements table
Description of the physical quantity Word (hex) Unit
Temperature measure 180 °C
Maximum temperature 181 °C
Minimum temperature (°C) 184 °C
Humidity measure (%) 187 %
Maximum humidity (%) 188 %
Minimum humidity (%) 18B %