Seagate ST100FP0021 Computer Drive User Manual


 
SEAGATE 600 PRO SSD PRODUCT MANUAL, REV. A 21
3.5 COOLING
Cabinet cooling must be designed by the customer so that the ambient temperature immediately surrounding the drive will
not exceed temperature conditions specified in Section 2.9.1, "Temperature."
The rack, cabinet, or drawer environment for the drive must provide heat removal. You should confirm that adequate heat
removal is provided using the temperature measurement guidelines described in Section 2.9.1.
Forced air flow may be required to keep temperatures at or below the temperatures specified in Section 2.9.1 in which case
the drive should be oriented, or air flow directed, so that the least amount of air flow resistance is created while providing air
flow to the drive. Also, the shortest possible path between the air inlet and exit should be chosen to minimize the travel length
of air heated by the drive and other heat sources within the rack, cabinet, or drawer environment.
If forced air is determined to be necessary, possible air-flow patterns are shown in Figure 4. The air-flow patterns are created
by one or more fans, either forcing or drawing air as shown in the illustrations. Conduction, convection, or other forced air-
flow patterns are acceptable as long as the temperature measurement guidelines of Section 2.9.1 are met.
Figure 4. Air flow
Image may not represent actual product, for reference only.
Above unit
Under unit
ote. Air flows in the direction shown (back to front)
or in reverse direction (front to back)
Above unit
Under unit
ote. Air flows in the direction shown or
in reverse direction (side to side)