Sierra 215 Switch User Manual


 
IM-215 Rev-A.1 Series Innova-Switch™ Page 31 of 42
The electronic assemblies contained in the Innova-Switch™ are configured for specific voltages
and have specific modifications to accommodate the various agency approvals. When ordering
spare electronics, replacements, or exchanges in the field please ensure you identify the specific
configuration you have by noting the boxes marked on the transformer configuration tag.
6.2.2 Sensor/Electronics Functionality Verification
1. Turn power off to Innova-Switch
.
2. Allow a 5 minute cool down.
3. Measure the resistance of each RTD at pins 1 and 6 of TBA (see Figure 6.0 or
7.0) for the hot RTD and pins 3 and 5 of TBA for the cold RTD. These
resistances should be 110 ± 10 ohms (with sensors at approximately 70°F) and
within 5% of each other in value.
4. Measure the insulation resistance between pin 1 of TBA and the case of the
Innova-Switch
. It should greater than 20 megohms.
5. If the Innova-Switch
sensor assembly resistances are not as specified above,
the switch sensor assembly must be replaced.
6. If the Innova-Switch
sensor assembly resistances are as specified, the Innova-
Switch
PC electronic board must be replaced.
SPECIAL NOTICE