Sony BKS-R3203 Network Router User Manual


 
5-47
ROUTING SWITCHER SYSTEM (E)
5-3. Setting Items of the Primary Station on Monitor S-BUS (BKDS-V3292B only)
SET MONITOR FUNCTION DVS-V6464B Monitor Bus I/F V2.10
MODIFICATION COMMAND
F: SET SCTIVE UNIT NUMBER
M: SELECT MONITOR FUNCTION (COMBINED)
R: CALL SECONDARY STATION
Ctrl-E:RETURN TO MENU
ENABLE ACTIVE UNIT FOR STATION NUMBER DVS-V6464B Monitor Bus I/F V2.10
1 2 3 4 5 6 7 8 9 10 1112131415 1617181920
+
001-020 M E E E E E E E E E E E E E E E E E E E
021-040 E E E E E E E E E E E E E E E E E E E E
041-060 E E E E E E E E E E E E E E E E E E E E
061-080 E E E E E
081-100
101-120
121-140
141-160
161-180
181-200
201-220
221-240
241-254 Å * * * * * *
CTRL-E:RETURN TO MENU
5-3. Setting Items of the Primary Station
on Monitor S-BUS (BKDS-V3292B
only)
Used for setting the units on the monitor S-BUS.
Menu Screen of the Primary Station on Monitor S-BUS
Setting Procedure of Monitor Function
1. Select the menu item [R] of the primary station in
order to call the menu screen of the secondary station
set as the primary station on the monitor S-BUS.
2. Select the menu item [M] to call the menu screen of
the primary station on the monitor S-BUS.
3. Set the menu item [F] and [M].
4. Select the menu item [R] to call the secondary station
on the monitor S-BUS.
5. Set each menu item on the screen.
6. Press [Ctrl] _ [Z] to return to the menu screen of the
primary station on the monitor S-BUS.
7. Set each item of all secondary stations, repeating the
procedure of step 4 to 6.
8. Press [Ctrl] _ [D] to return to the menu screen of the
primary station on the standard S-BUS.
n
If there are multiple monitor S-BUS data links, repeat the
procedure of step 1 to 8 for each link.
F : SET ACTIVE UNIT NUMBER
Purpose
This menu is used to enable the units connected to the data
link of the monitor S-BUS to communicate.
Setting Procedure
1. Select menu item [F].
2. Select the secondary station using the cursor whose
communication will be valid.
3. When [Enter] is pressed, the setting displayed will
change “E” “Blank” “E”. Only the secondary
stations displayed with “E” are valid. (“M” indicates
the primary station.)
4. When [Ctrl] _ [E] is pressed, the menu screen of the
primary station on the monitor S-BUS will be dis-
played.
n
As the response will become slower if there are many
secondary stations, make the secondary stations not
connected invalid.
*” indicates out of the control area.
Example of Setting Screen
m
1. Station ID of the primary station is always 1 regardless
of the DIP switch setting on the CPU board.
2. Station ID of the secondary station is deter mined with
the DIP switch setting. Do not assign the same
number on two or more units as station ID on both
standard S-BUS and monitor S-BUS.
Number that can be registered as secondary s station
ID are 2 to 254.