Sun Microsystems X4200 M2 Network Card User Manual


 
2 Sun Fire X4100/X4100 M2 and X4200/X4200 M2 Servers Installation Guide May 2007
5. Configure the preinstalled Solaris™ operating system or install a supported
operating system of your choice. For details, refer to one of the following:
“Configuring the Preinstalled Solaris 10 Operating System” on page 36
Sun Fire X4100/X4100 M2 and X4200/X4200 M2 Servers Operating System
Installation Guide, 819-1158
Sun Fire X4100/X4100 M2 and X4200/X4200 M2 Servers Windows Operating
System Installation Guide, 819-4346
6. Customize your server as needed. For details, refer to the “System Management”
section of the online information system or the Integrated Lights-Out Manager
Administration Guide, 820-0280-10.
Installing the Server Into a Rack With
Optional Slide Rails
To install your server in a four-post rack using the orderable slide-rail option, follow
these procedures. These slide-rails are compatible with a wide range of equipment
racks that meet the following standards:
Four-post structure (mounting at both front and rear). Two-post racks are not
compatible.
Rack horizontal opening and unit vertical pitch conforming to ANSI/EIA
310-D-1992 or IEC 60927 standards.
Distance between front and rear mounting planes between 610 mm and 915 mm
(24 inches to 36 inches).
Clearance depth (to front cabinet door) in front of front rack mounting plane at
least 25.4 mm (1 inch).
Clearance depth (to rear cabinet door) behind front rack mounting plane at least
800 mm (31.5 inches) or 700 mm (27.5 inches) without cable management arm.
Clearance width (between structural supports and cable troughs) between front
and rear mounting planes at least 456 mm (18 inches).
Note – Although the Sun Fire X4100/X4100 M2 server is pictured in the illustrations
in this section, these procedures also apply to the Sun Fire X4200/X4200 M2 server.
Caution – Always load equipment into a rack from the bottom up so that it will not
become top-heavy and tip over. Deploy your rack’s anti-tilt bar to prevent the rack
from tipping during equipment installation.