Technicolor - Thomson TS 870 Switch User Manual


 
TS 870 TRANSFER SWITCH
PM062 REV 5 08/05/05 27 Thomson Technology
15. CABLE TERMINAL INFORMATION
TERMINAL RATING
CONNECTION TIGHTNESS
(In-lbs)
BASIC MODEL
QTY
PER
PHASE
RANGE
TERMINAL
MOUNTING
SCREW
CABLE
CLAMP
TS 87xA-0100 1 #14-1/0
120 50
TS 87xA-0150 1 #2–4/0
120 120
TS 87xA-0200 1 #6–350MCM 150 275
TS 87xA-0250 1 #6–350MCM 150 275
TS 87xA-0400
1
2 2/0–500MCM 72 275
TS 87xA-0600
1
2 2/0–500MCM 72 275
TS 87xA-0800
1
3 2/0–500MCM 110 375
TS 87xA-1200
1
4 4/0–500MCM 375 375
1. Optional terminal ratings are available in some models – Consult Thomson Technology.
2. For other model types not shown, contact Thomson Technology for further information.
16. REQUIREMENTS FOR UPSTREAM CIRCUIT PROTECTIVE DEVICES
16.1. WITHSTAND CURRENT RATINGS (ALL MODELS WITHOUT INTEGRAL
OVERCURRENT PROTECTION OPTION)
WITHSTAND CURRENT RATING AMPS (RMS)
1
With Upstream Circuit Breaker Protection With Upstream Fuse Protection
BASIC MODEL
MAX.
VOLTAGE
RATED
CURRENT
(A)
@240V @480V @600V @ Up to 600V Fuse Type
TS87xA-0100
600 100 65,000 25,000 18,000 100,000 T, J
TS87xA-0150
600 150 65,000 25,000 18,000 100,000 T, J
TS87xA-0200
240 200 65,000 N/A N/A N/A T, J
TS87xA-0250
600 250 65,000 35,000 25,000 100,000 T, J
TS87xA-0400
600 400 65,000 50,000 35,000 100,000 T, J
TS87xA-0600
600 600 65,000 50,000 35,000 100,000 T, J
TS87xA-0800
600 800 65,000 50,000 35,000 100,000 Consult Factory
TS87A-1000/1200
600 1000/1200 65,000 50,000 42,000 100,000 Consult Factory
1.
Standard ratings only are shown. Consult Thomson Technology for versions with higher withstand current ratings.
2.
For other model types not shown, contact Thomson Technology for further information.
Fuse ratings shown are maximum allowable to permit use of the transfer switch in application with
available fault current not exceeding that shown. Consideration must be given to fuse sizing when
fuses also provide overload protection.