Toshiba 1500 Plus Power Supply User Manual


 
TOSHIBA
4 - 1
4.1 Standard Series Specifications
4.0 Specifications
MODEL NUMBER UE1E1E008-5M UE1E1E010-5M
CAPACITY 800 VA (0.56 kW) 1000 VA (0.7 kW)
Input Input voltage Single phase, 220 Vac, +10% to -30% (*)
Input frequency 45 to 65 Hz
Input capacity 800 VA 1000 VA
Input power factor Approximate unity (0.95 to 1.0)
Battery Battery rated voltage 60 Vdc
Battery backup time when fully charged
8 min. at full load (**) 7 min. at full load (**)
with 0.7 power factor at 77° F (25° C)
20 min. at half load (**) 18 min. at half load (**)
Recharge time Maximum 24 hrs to 100% (90% recharge after 8 hrs) (***)
Type of batteries Sealed lead-acid
Output Output voltage Single-phase, 220 volts
Output voltage regulation Within +/- 3%, steady state
Output frequency 50/60 Hz +/- 0.5% in free-running mode (line sync range +/- 1Hz)
Output voltage waveform Computer-grade sine wave with less than 3.0% total harmonic
distortion with linear load
Rated load power factor 0.7 lagging (0.6 to 1.0)
Voltage transient characteristic +/- 8% under 100% load step change
Rated output current (rms) 3.6A 4.5A
Maximum output current (peak) 10.8A 13.5A
Inverter overload capacity 150% for 30 seconds
Crest factor 3.0
Environment Operating temperature 32 to 104° F (0 to 40° C), optimal at 77° F (25° C)
Storage temperature -4 to 104° F (-20 to 40° C)
Operating humidity 30 to 90%, no condensation
Altitude(****) Less than 3000 ft (1000 m) above sea level
External dimensions 8.00W x 20.38D x 10.00H in (203W x 518D x 254H mm)
Net weight 58.8 lb (26.7 kg) 60.7 lb (27.5 kg)
Acoustical noise 50 dB at max. output, measured 3.3 ft (1 m) from front panel
Efficiency (ac-dc-ac) 85% 87%
Switches Bypass switch Automatic bypass is provided when the run switch is in the stop
position, if a fault occurs, or if an overload occurs (transfer time is
approximately 4 msec)
Interfaces IBM
(TM)
AS/400
LAN Manager See section 6.0 for details.
Fault detect and input power loss
RS232 ASCII
Options Software for unattended
computer shutdown Contact Toshiba for details on this option
External battery pack Contact Toshiba for details on this option
(*) Output capacity reduced when input voltage is between -15% and -30% of nominal.
(**) Battery backup time may vary depending on the operating conditions including ambient temperature at the
installation site.
(***) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is used
for battery backup.
(****) Above 3000 ft (1000 m), output capacity reduced.