Toshiba 1600EP Power Supply User Manual


 
19
1600EP Series Instruction Manual
kVA; 14kVA; 18KVA; 22kVA (CONT’D)
Capacity 10 kVA (8.5 kW)
1
14 kVA (11.9 kW)
1
18 kVA (15.3 kW)
1
22 kVA (18.7 kW)
1
Environment
Operating temperature
(15 – 25° C recommended)
60 Hz (0 – 40 °C) ; 50Hz (0 – 33 °C)
Storage Temperature -20 – 40 °C (-4 – 104 °F)
Installation Area
To be installed in a well ventilated area free of airborne dust,
metal particles or ammable gas, allow at least 4 inches on all sides
Operating Humidity 30 – 90% (no condensation)
Altitude < 3200 ft. (1000 m) above sea level
2
Acoustical Noise 50 dB (A) maximum @ 1 meter from front panel
Heat Generation 4352 BTU/Hr 6092 BTU/Hr 7832 BTU/Hr 9600 BTU/Hr
Operation Diagnosis
Battery Check Performed on start up, by schedule, on-demand (user congurable)
Input OV Protection Standard
Battery Lifetime
UPS calculates battery replacement time based upon
battery ambient temperature (LCD display, LED and beeps)
Internal Temperature UPS gives indication of internal temperature, alarm when high temp
Event Data Storage 64-Supply Mode, 32-Back up, 16-Faults
Applications
Switches Generator compatible
Bypass Switch
Bypass Disable Static switch <1/4 cycle (50Hz: 5 ms/60Hz: 4.16 ms)
Automatic Retransfer Factory or authorized service center selectable only
User Interface Provided – Can be disabled from front panel
Real Time Clock
Schedule Operation Standard – Minimum 3 days memory backup during power loss
RUN/STOP Disable Schedule ON/OFF operation of UPS using communication software
Autostart UPS has option for UPS to start automatically when AC is applied
Remote ON/OFF Standard – External terminal
LED Display 4 LED’s indicating input/output condition, warning and battery operation
LCD Screen 16 characters x 2 lines
UPS Operation: 6 Keys Run/Stop, Set/Monitor, Shift/Select, Del/(page down), Reset/(page up)
Buzzer Volume Low, High, Mute; Selectable by keypad
Power Connections Standard – Hard wire
Emergency Power Off Standard – Terminal contacts only
Remote Contacts Standard (INV, BYP, BATT, LB, AC, FLT)
RS232 ASCII Interface Standard
1. input voltage is
greater than 204 volts; otherwise, ratings given for 0.70PF are applicable.
At 6600 ft (2000 m) above sea level, output capacity should be derated by 3%2.