Inverter operating status 1 (FD01, FE01)
Inverter status 1 (current status): Communication Number FD01
Inverter status 1 (status immediately before the occurrence of a trip): Communication Number FE01
Bit Specifications 0 1 Remarks
0 Failure FL No output Output in progress
1 Failure Not tripped Tripped Trip statuses include
and trip retention status.
2 Alarm No alarm Alarm issued
3 Reserved - -
4 Motor section (1 or 2)
(THR 2 selection)
Motor 1 (THR 1) Motor 2 (THR 2)
5 PI control OFF PI control
permitted
PI control
prohibited
6 Accelera-
tion/deceleration
pattern selection (1 or
2)
Acceleration/
deceleration
pattern 1 (AD 1)
Acceleration/
deceleration pat-
tern 2 (AD 2)
AD1 :,
AD2 :,
7 DC braking OFF Forced DC braking
8 Jog run OFF Jog run
9 Forward/reverse run Forward run Reverse run
10 Run/stop Stop Run
11 Coast stop (ST=OFF) ST=ON ST=OFF
12 Emergency stop Not emergency
stop status
Emergency stop
status
13 Standby ST=ON Start-up process Standby Standby: Initialization completed,
not failure stop status, not alarm
stop status (MOFF, LL forced
stop or forced stop due to a
momentary power failure),
ST=ON, and RUN=ON
14 Standby Start-up process Standby Standby: Initialization completed,
not failure stop status, and not
alarm stop status (MOFF, LL
forced stop or forced stop due to
a momentary power failure)
15 Reserved - -