Trane BACnet Option Module Computer Drive User Manual


 
How to Configure the System
Configuring BACnet
Initialization Procedure
The Initialization Procedure is explained by the flow chart given below:
Initialization Parameter
General Settings
Name
Par. Number Default Value Setting for BACnet
Control Site 8-01 Digital and control word Digital and control word
Control word source 8-02 Drive RS-485 Drive RS-485
ControlWord Timeout time 8-03 1.0 sec 1.0 sec
ControlWord Timeout Function 8-04 Off Off
End of Timeout Function 8-05 Resume set-up Resume set-up
Reset ControlWord Timeout 8-06 Do not reset Do not reset
Diagnosis 8-07 Set-up Don’t care
ControlWord Profile 8-10 Drive Profile Drive Profile
Drive Port Settings
Name Par. Number Default Value Setting for BACnet
Protocol 8-30 Drive Drive Option
Address 8-31 1 1
Baud Rate 8-32 9600 baud 9600 baud
Minimum Response Delay 8-35 10 ms 10 ms
Max Response Delay 8-36 5000 ms 5000 ms
Table 4. 1: 1) Please see also section: Parameter Overview >Parameter List.
TR200 BACnet 4-1