Trane BACnet Option Module Computer Drive User Manual


 
Object
ID
Object Name
Read /
Write
Change-
able De-
scription
Non-vola-
tile RAM
Store
Drive Par.
Alarm
notifi-
cation
Triggers Bus
Timeout
BV:0 Com. Fault R No NA
BACnet op-
tion
Yes No
BV:1 Start W/R No No CTW No Yes
BV:2 Coasting W/R No No
CTW, Bit 3
=0
No Yes
BV:3 CW/CCW W/R No No
CTW bit
15=1
No Yes
BV:4 Jog W/R No No
CTW bit 0
=1
No Yes
BV:5 Reset W No No
CTW bit 07
= 1
No Yes
BV:6
Reset Kwh Coun-
ter
W No No P15-06 No NO
BV:7
Reset Running
Hours Counter
W No No P15-07 No NO
BV:10 Drive Ready R No NA STW Bit 01 No No
BV:11 Reverse R No NA STW Bit 15 No No
BV:12
Speed = Refer-
ence
R No NA STW Bit 08 No No
BV:13 Bus Control R No NA STW Bit 09 No No
BV:14 Tripped R No NA STW Bit 03 Yes No
BV:15 Triplock R No NA STW Bit 06 Yes No
BV:16 -20 Reserved R No
BV:21 ECB Test Mode R No NA 31-10/00 No No
BV:22 ECB Drive mode R No NA 31-10/01 No No
BV:23
ECB Aut. Bypass
Enable
R No NA 31-10/02 No No
BV:24
ECB Bypass
Mode
R No NA 31-10/03 No No
BV:25 ECB State R No NA 31-10/05 Yes No
BV:26
ECB Overload
Trip
R No NA 31-10/06 Yes No
BV:27 M2 Fault R No NA 31-10/07 Yes No
BV:28 M3 Fault R No NA 31-10/08 Yes No
BV:29
ECB External In-
terlock
R No NA 31-10/09 Yes No
BV:30
ECB Manual
Override
R No NA 31-10/10 No No
BV:31 Reserved R No
Table 5. 8: Binary values
How to Control the Adjustable Frequency
Drive
5-8 TR200 BACnet