Trane BACnet Option Module Computer Drive User Manual


 
Object / Property Support Matrix, continued..
Property Device
Binary
input
Binary
output
Binary
value
Analog
input
Analog
output
Analog
value
Multi-
stage
value
File
Event
notifi-
cation
class
Present Value X X X X X X
Status Flags X X X X X X
Event State X X X X X X
Reliability X X X X X X
Out-of-Serv-
ice
XXXXX X
Number of
States
X
State Text X
Units X X X
Time Delay X X
Notification
Class
X X
High Limit X X
Low Limit X X
Deadband X X
Limit Enable X X
Event Enable X X
Acked Transi-
tions
X X
Notify Type X X
Event Time
Stamp
X X
Priority Array X X* X ?? X
Priority X
ACk Required X
Recipient List X
# of Notifica-
tion Class
X
Relinquish De-
fault
X X* X ?? X
Polarity X X
Active Text X X X
Inactive Text X X X
File type X
File size X
Modification
Date
X
Archive X
Read Only X
File Access
Method
X
*For commandable values only
How to Control the Adjustable Frequency
Drive
TR200 BACnet 5-17