9Smart-UPS 750/1000/1500/2200/3000 VA 100/120/230 Vac / 500 VA 100 Vac Tower
Low Transfer Point
100 Vac:
92 Vac
86 Vac - 92 Vac
Set the transfer point lower if the utility voltage is
chronically low and the connected equipment can
tolerate this condition.This setting may also be adjusted
using the power quality setting.
Note: Use the Advanced Menus to configure this
setting.
120 Vac:
106 Vac
97 Vac - 106 Vac
230 Vac:
208 Vac
196 Vac -208 Vac
Nominal Output
Voltage
100 Vac N/A
230 Vac models only: Set the nominal output voltage of
the UPS to standby mode.
120 Vac N/A
230 Vac
• 220 Vac
• 230 Vac
• 240 Vac
Transfer Sensitivity Normal Normal, Reduced, Low
Select the level of sensitivity to power events that the
UPS will tolerate.
• Normal: The UPS will go on battery power more
often to provide the cleanest power supply to the
connected equipment.
• Low: The UPS will tolerate more fluctuations in
power and will go on battery power less often.
If the connected load is sensitive to power disturbances,
set the sensitivity to Normal.
Low Battery Warning 120 sec Set the value in seconds
The UPS will emit an audible alarm when the remaining
runtime has reached this level.
Date of Last Battery
Replacement
Date set at factory Reset this date when the battery module is replaced.
Audible Alarm On On/Off
The UPS will mute all audible alarms if this is set to Off
or when the display keys are pressed.
Battery
Self-Test Interval
Setting
On start up and every
14 days since the last
test
•Never
• Start up only
• Frequency of test
(every 7 to 14 days)
The interval at which the UPS will execute a
self-test.
Reset to Factory
Default
No Yes/No Restore the UPS factory default settings.
Function Factory Default Options Description