11Smart-UPS 750/1000/1500/2200/3000 VA 100/120/230 Vac / 500 VA 100 Vac Tower
Customize the Main and Controlled Outlet Groups
Use the Configuration menus to change the Main Outlet Group and the Controlled Outlet Group settings.
Network Management Card Settings
These settings are available only on units that have a Network Management Card (NMC) and are set at the factory.
These settings can only be modified using an external interface, such as the NMC Web interface.
• NMC IP Address Mode
• NMC IP Address
• NMC Subnet Mask
• NMC Default Gateway
Function Factory Default Options Description
Name String
Outlet Group
Outlet Group 1
Edit these names using an external interface, such as the Network
Management Card Web interface.
UPS Name String UPS Outlets
Turn On Delay 0 sec
Set the value in
seconds
The amount of time the UPS or a Controlled Outlet
Group
will wait between receiving the command to
turn on and the actual startup.
Turn Off Delay
• 0 sec UPS Outlets
• 90 sec Controlled
Outlet Groups
Set the value in
seconds
The amount of time the UPS or a Controlled Outlet
Group
will wait between receiving the command to
turn off and the actual shut down.
Reboot Duration 8 sec
Set the value in
seconds
The amount of time the UPS or a Controlled Outlet
Group
must remain off before it will restart.
Minimum Return
Time
0 sec
Set the value in
seconds
The amount of battery runtime that must be available
before the UPS or
a Controlled Outlet Group will
turn on after a shutdown.
Load Shed On
Battery
Disabled
• Enable
• Disable
When the unit switches to battery power, the UPS
will disconnect power to the
Controlled Outlet
Group
to save battery runtime.
Configure this delay time, use the
LOAD SHED TIME
WHEN ON BATTERY setting.
Load Shed Time
when On Battery
1800 sec
Set the value in
seconds
The amount of time the outlets will function on
battery power before they will turn off.
Load Shed On
Runtime
Disabled
• Enable
• Disable
When the battery runtime falls below the specified
value, the
Controlled Outlet Group will turn off.
Configure this time using the
LOAD SHED RUNTIME
REMAINING setting.
Load Shed On
Runtime
Remaining
120 sec
Set the value in
seconds
When the remaining runtime reaches this level, the
Controlled Outlet Group will turn off.
Load Shed on
Overload
Disabled
• Disabled
• Enabled
In the event of an overload (greater than 107%
output), the
Controlled Outlet Group will
immediately turn off to conserve power for critical
loads. The Controlled Outlet Group
will only turn on
again with a manual command.