Specifications
11
Tripp Lite has a policy of continuous improvement.Specifications are subject to change without notice.
SmartPro SLT UPS Systems
Model: SMART1050SLT SMART1500SLT
Series #: AGSM1000DT AGSM1500DT
Input
Nominal Voltage:* 100, 110, 120 or 127 VAC 100, 110, 120 or 127 VAC
Frequency (± 3 Hz.): 60 Hz. 60 Hz.
Recommended Dedicated Electrical Circuit: 15 amp 15 amp
Output
Nominal Voltage:* 100, 110, 120 or 127 VAC 100, 110, 120 or 127 VAC
Frequency (± 3 Hz.): 60 Hz. 60 Hz.
Capacity (VA/Watts)
@ 127 VAC: 1050/670 1500/950
@ 120 VAC: 1050/670 1500/950
@ 110 VAC: 945/603 1350/855
@ 100 VAC: 840/536 1200/760
Waveform (Line and Battery Modes): sine wave sine wave
Maximum Harmonic Distortion (Linear Load/Non-Linear Load): < 3% / < 6% < 3% / < 6%
Battery
Battery Runtime (Half Load/Full Load) Minutes: 20/7 20/8
Battery Recharge Time (to 80% Capacity): 2-4 hours 2-4 hours
Transfer Time: 4-8 milliseconds 4-8 milliseconds
Battery System Voltage: 36 VDC 36 VDC
FCC: Class B Class B
Approvals: UL, cUL, NOM UL, cUL, NOM
SmartPro XL UPS System
Model: SMART750XL
Series #: AGSM751ST
Input
Nominal Voltage:* 100, 110, 120 or 127 VAC
Frequency (± 3 Hz.): 60 Hz.
Recommended Dedicated Electrical Circuit: 15 amp
Output
Nominal Voltage:* 100, 110, 120 or 127 VAC
Frequency (± 3 Hz.): 60 Hz.
Capacity (VA/Watts)
@ 127 VAC: 750/450
@ 120 VAC: 750/450
@ 110 VAC: 675/430
@ 100 VAC: 600/382
Waveform (Line and Battery Modes): sine wave
Maximum Harmonic Distortion (Linear Load/Non-Linear Load): < 3% / < 6%
Battery
Battery Runtime (Half Load/Full Load) Minutes: 33/10+
Battery Recharge Time (to 80% Capacity): 2-4 hours
Transfer Time: 4-8 milliseconds
Battery System Voltage: 36 VDC
FCC: Class B
Approvals: UL, cUL, NOM
* A set of user-selectable Voltage DIP Switches (see Quick Installation section) match the UPS system's output voltage to the input voltage available at the
wall outlet.
+ Battery runtime can be extended with the addition of optional Tripp Lite External Battery Packs (sold separately). SMART750XL models use BP36V27
battery packs. External batteries will increase both the battery runtime and the battery recharge time.
10
Storage
First turn your UPS OFF: press the “OFF” switch to turn power off at the outlets, then discon-
nect the power cord from the wall outlet. Next, disconnect all equipment to avoid battery drain.
If you plan on storing your UPS for an extended period of time, fully recharge the UPS bat-
teries once every three months by plugging the UPS into a live AC outlet and letting the UPS
charge for 4-6 hours. If you leave your UPS batteries discharged for an extended period of
time, they may suffer permanent loss of capacity.
Service
Before returning your UPS for service, follow these steps:
1. Review the installation and operation instructions in this manual to ensure that the service
problem does not originate from a misreading of the instructions. Also, check that the UPS
System’s circuit breaker(s) are not tripped. This is the most common cause of service
inquiries which can be easily remedied by following the resetting instructions in this manu-
al.
2. If the problem continues, do not contact or return the UPS to the dealer. Instead, call Tripp Lite
at (773) 869-1233. A service technician will ask for the UPS’s model number, serial number
and purchase date and will attempt to correct the problem over the phone.
3. If the problem requires service, the technician will issue you a Returned Material
Authorization (RMA) number, which is required for service. If you require packaging, the
technician can arrange to send you proper packaging. Securely pack the UPS to avoid damage
during shipping. do not use Styrofoam beads for packaging. Any damages (direct, indirect,
special, incidental or consequential) to the UPS incurred during shipment to Tripp Lite or an
authorized Tripp Lite service center is not covered under warranty. UPS Systems shipped to
Tripp Lite or an authorized Tripp Lite service center must have transportation charges prepaid.
Mark the RMA number on the outside of the package. If the UPS System is within the 2-year
warranty period, enclose a copy of your sales receipt. Return the UPS for service using an
insured carrier to the address given to you by the Tripp Lite service technician.
Storage and Service