Tripp Lite 93-2007 (200106010) Power Supply User Manual


 
10
APS systems must be connected to a grounded, permanent wiring system. For most installations,
the negative battery conductor must be bonded to the grounding system at one (and only one)
point in the system. All installations must comply with national and local codes and ordinances.
When figuring the power requirements of your equipment, do not confuse “continuous” power
ratings with “peak” power ratings. Electric motors require more power to turn on (“peak power”)
than they require to run continuously. “Peak” power ratings are usually 2 to 5 times
“Continuous” ratings. Most electric motors require “peak power” only when they are first turned
on. The electric motors in equipment such as refrigerators and sump pumps, however, constantly
turn on and off according to demand. These motors require “peak power” at multiple, unpredictable
times during their operation.
Consult a qualified electrician and follow all applicable electrical codes and requirements.
HARDWIRE PROCEDURE
1. Remove screws and cover plate from your APS’s Hardwire AC electrical box. Remove the
knockout covers closest to the desired electrical source and to your equipment.
2. Thread your wires through strain reliefs and through the knockouts.
3. Connect all input and output ground wires to the input/output ground tie point.
4. Connect the incoming hot wire to the input hot (brown) terminal.
5. Connect the incoming neutral wire to the input neutral (blue) terminal.
6. Connect the outgoing hot wire to the output hot (black) terminal.
7. Connect the outgoing neutral wire to the output neutral (white) terminal.
8. Tighten and affix strain reliefs. Replace cover plate and tighten screws.
This IEC receptacle should be connected to a dedicated 15 Amp AC utility outlet that provides
a connection to ground. A detachable IEC cord is provided for this purpose. Plug it into an outlet
providing 230V AC power at 50 Hz. A user-supplied adapter that maintains the UPS’s connection
to ground may be necessary. (A technician may be able to convert your APS to receive 60 Hz.
power. Consult Tripp Lite for details.) Make sure that the circuit you connect your APS to has
adequate overload protection, such as a circuit breaker or a fuse.
Battery Connection
continued
DC Ground Connection
AC Connection
Before AC connection, match the power requirements of your
equipment with the power output of your APS to avoid overload.
Hardwired Electrical Connections
(All hardwire models)
(See Diagram 3, p. 36)
AC Input Electrical Connection
(All corded models)
200106010 230V APS Owners Manual.qxd 1/3/02 5:18 PM Page 10