Tripp Lite 93-2007 (200106010) Power Supply User Manual


 
16
Specifications
(Corded Models)
CORDED MODELS: APSINT1012
Weight: 11.9 Kg
INVERTER
Continuous power (@ 20° C): 1000 W
Surge power (5 seconds): 2000 W
Efficiency (Full Load): 88%
Minimum DC Fuse Rating: 170A
DC Input Current @ Nominal V DC
Full Load 95A
No Load 2.6A*
Nominal Input Volts: 12 VDC
DC Input Voltage Range: 10-15 VDC
Nominal Output Volts: 230 VAC ±5%
Nominal Output Frequency: 50† Hz ±.3%
BATTERY CHARGER
Charging Capacity DC: 30 A
Maximum Cable Length 2 ft.
Acceptance Volts VDC: Selectable
14.4 V**/14.2 V Wet**/Gel
Float Volts VDC (w/gel): 13.3 V (13.6 V)
Input Voltage AC: 230 V
Input Current AC: 3.3 A
LINE VAC OPERATION
Minimum Input AC Volts: Selectable 144**,163, 182 or 201VAC
Maximum Input AC Volts
(Continuous, Charger at Maximum): Selectable 259** or 264 VAC
Maximum Input Current
(Continuous, Charger at Maximum): 12.0 A
Input Frequency: 50 Hz ±10%
Maximum Output AC (Continuous): 4.3 A
Automatic Transfer Time: 4-6 ms
* Load sense can reduce this to 1/30 of the listed current. **Factory default setting.
† A technician may be able to convert your UPS to receive 60 Hz ±10%power. Consult Tripp Lite for details.
200106010 230V APS Owners Manual.qxd 1/3/02 5:18 PM Page 16