Tripp Lite 93-2007 (200106010) Power Supply User Manual


 
17
Specifications
(Hardwired Models)
HARDWIRED MODELS: APSINT1524 APSINT2012
Weight: 12.7 Kg 17.1 Kg
INVERTER
Continuous power (@ 20° C): 1500 W 2000 W
Surge power (5 seconds): 3000 W 4000 W
Efficiency (Full Load): 89% 87%
Minimum DC Fuse Rating: 90A 370A
DC Input Current @ Nominal V DC
Full Load 70A 192 A
No Load 1.5A* 3 A*
Nominal Input Volts: 24 VDC 12 VDC
DC Input Voltage Range: 20-30 VDC 10-15 VDC
Nominal Output Volts: 230 VAC ±5% 230 VAC ±5%
Nominal Output Frequency: 50† Hz ±.3% 50† Hz ±.3%
BATTERY CHARGER
Charging Capacity DC: 10 A** 60 A
Maximum Cable Length 7 ft. 1 ft.
Acceptance Volts VDC: Selectable Selectable
28.8 V**/28.4 V Wet**/Gel 14.4 V**/14.2 V Wet**/Gel
Float Volts VDC (w/gel): 26.6 V (27.2 V) 13.3 V (13.6 V)
Input Voltage AC: 230 V 230 V
Input Current AC: 2.2 A** 7.0 A
LINE VAC OPERATION
Minimum Input AC Volts: Selectable 144**, 163, 182 or 201 VAC Selectable 144**,163, 182 or 201 VAC
Maximum Input AC Volts
(Continuous, Charger at Maximum): Selectable 259** or 264 VAC Selectable 259** or 264 VAC
Maximum Input Current
(Continuous, Charger at Maximum): 13.0 A 16 A
Input Frequency: 50 Hz ±10% 50 Hz ±10%
Maximum Output AC (Continuous) 6.5 A 8.7 A
Automatic Transfer Time: 4-6 ms 4-6 ms
HARDWIRED MODELS (Cont.): APSINT2424 APSVRI3636
Weight: 18.5 Kg 25.6 Kg
INVERTER
Continuous power (@ 20° C): 2400 W 3600 W
Surge power (5 seconds): 4800 W 7200 W
Efficiency (Full Load): 89% 88%
Minimum DC Fuse Rating: 220A 130A
DC Input Current @ Nominal V DC
Full Load 112 A 114 A
No Load 1.8 A* 2 A*
Nominal Input Volts: 24 VDC 36 VDC
DC Input Voltage Range: 20-30 VDC 30-45 VDC
Nominal Output Volts: 230 VAC ±5% 230 VAC ±5%
Nominal Output Frequency: 50† Hz ±.3% 50† Hz ±.3%
BATTERY CHARGER
Charging Capacity DC: 30 A 30 A
Maximum Cable Length 3 ft. 4.5 ft.
Acceptance Volts VDC: Selectable Selectable
28.8 V**/28.4 V Wet**/Gel 43.2 V**/42.6 V Wet**/Gel
Float Volts VDC (w/gel): 26.6 V (27.2 V) 39.9 V (40.8 V)
Input Voltage AC: 230 V 230 V
Input Current AC: 7.0 A 10.4 A
LINE VAC OPERATION
Minimum Input AC Volts: Selectable 144**,163, 182 or 201 VAC Selectable 144**,163, 182 or 201 VAC
Maximum Input AC Volts
(Continuous, Charger at Maximum): Selectable 259** or 264 VAC Selectable 259** or 264 VAC
Maximum Input Current
(Continuous, Charger at Maximum): 17.0 A 26.0 A (30.0 A***)
Input Frequency: 50 Hz ±10% 50 Hz ±10%
Maximum Output AC (Continuous) 10.4 A 15.7 A
Automatic Transfer Time: 4-6 ms 4-6 ms
*Load sense can reduce this to 1/30 of the listed current. **Factory default setting. ***When AVR is boosting incoming
current.†A technician may be able to convert your UPS to receive 60 Hz ±10%power. Consult Tripp Lite for details.
200106010 230V APS Owners Manual.qxd 1/3/02 5:18 PM Page 17