Tripp Lite SMX3000XLRT2U Power Supply User Manual


 
Nominal Input Voltage(s)
Supported
230V AC
UPS input connection type C20 inlet
UPS input connection
description
IEC320-C20 input connection accepts a variety of detachable cordsets to match country or site-specific wall
receptacles
Input circuit breaker 20A
BATTERY
Full load runtime (minutes) 4 min. (2250w)
Half load runtime
(minutes)
11 min. (1125w)
Expandable battery
runtime
Extended runtime supported via optional external battery packs
External battery pack
compatibility
BP48V24-2U (limit 1); BP48V60RT-3U (multi-pack compatible)
DC system voltage (VDC) 48
Battery recharge rate
(included batteries)
Less than 4.5 hours from 10% to 90%
Replacement battery
cartridge (internal UPS
battery replacement)
RBC94-2U
Battery Access Front panel battery access door
Battery replacement
description
Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage regulation
description
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 158 to 278
Overvoltage correction Input voltages between 244 and 278 are reduced by 12%
Undervoltage correction Input voltages between 182 and 206 are boosted by 12%
Severe undervoltage
correction
Input voltages between 158 and 182 are boosted by 24%
LEDS ALARMS & SWITCHES
LED Indicators 5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
Alarms Audible alarm indicates power-failure, overload and low-battery conditions
Alarm cancel operation Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate
low-battery status
Switches 2 Switches control off/on power status and alarm-cancel/self-test operation; Rear dip-switch for charger rate
adjustment
SURGE / NOISE SUPPRESSION
UPS AC suppression
joule rating
480
UPS AC suppression
response time
Instantaneous
EMI / RFI AC noise
suppression
Yes