Tripp Lite SMX3000XLRT2U Power Supply User Manual


 
PHYSICAL
Installation form factors
supported with included
accessories
4 post 19 inch rackmount (mounting rail kit included)
Installation form factors
supported with optional
accessories
2 post rackmount (2POSTRMKITWM); Wallmount (2POSTRMKITWM); Tower (2-9USTAND); 2-4 post front rail
rackmount (UPSHDEARKIT)
Primary form factor Rackmount
UPS / Power Module
dimensions in primary
form factor (height x width
x depth / inches)
3.5 x 17.5 x 19
UPS / Power Module
dimensions in primary
form factor (height x width
x depth / cm)
8.9 x 44.4 x 48.3
Installed whole system
total rack space height
(rack spaces)
2U
Secondary form factor Tower (requires 2-9USTAND)
UPS / Power Module
weight (lbs)
64
UPS / Power Module
weight (kg)
29.1
UPS Shipping dimensions
(height x width x depth /
inches)
9 x 23.5 x 20
UPS Shipping dimensions
(height x width x depth /
cm)
22.9 x 59.7 x 50.8
Shipping weight (lbs) 72
Shipping weight (kg) 32.7
UPS housing material Steel
Cooling method Fan
ENVIRONMENTAL
Operating Temperature
Range
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature
Range
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity 0 to 95%, non-condensing
AC mode BTU / hr. (full
load)
236.6
Battery mode BTU / hr.
(full load)
1245.3
COMMUNICATIONS
Communications interface USB; DB9 Serial
Network monitoring port
description
Supports detailed monitoring of UPS and site powe.r conditions; 1 USB port and 1 DB9 serial port.