Western Telematic IPS-800CE-D16, IPS-1600CE-D16 Switch User Manual


 
Apx-2
IPS-800CE-D16 & IPS-1600CE-D16 - User’s Guide
B. Specifications
Power Input / Output:
AC Input: Two Separate Circuits; 16 Amps Max. per Circuit
Voltage: 100 - 240 VAC 50/60 Hz
Connectors: Two (2) IEC320-C20 Inlets
AC Outputs:
Connectors: IEC320-C13 Outlets. (IPS-800CE-D16 has Eight
Outlets, IPS-1600CE-D16 has 16 Outlets.)
Load: 10 Amps per Outlet. 16 Amps per Circuit; providing a
Total of 32 Amps for both circuits.
Control Ports:
Ethernet Port: 10Base-T
COM Port: DB9M, RS232C, DTE
RS232 Coding: Serial ASCII, 7/8 Bits
Physical / Environmental:
Size: IPS-800CE-D16
Width: 17.5” (44.5 cm) Standard Rack
Depth: 7.0” (17.8 cm)
Height: 1.75” (4.5 cm) 1 Rack U
Size: IPS-1600CE-D16
Width: 17.5” (44.5 cm) Standard Rack
Depth: 7.0” (17.8 cm)
Height: 3.5” (8.9 cm) 2 Rack U
Shipping Weight:
IPS-800CE-D16: 10 lbs (4.5 Kg)
IPS-1600CE-D16: 12 lbs (5.5 Kg)
Operating Temperature: 32°F to 122°F (0°C to 50°C)
Humidity: 10 - 90% RH