Xantrex Technology XPD 60-9 Power Supply User Manual


 
Section 1. Features and Specifications
Environmental Specifications
Release A 21
Environmental Specifications
Mechanical Specifications
Operating Temperature Range 0 to 50 °C
Storage Temperature Range -40 to 85 °C
Humidity Range Up to 95% RH non-condensing
Operating Altitude Maximum 6,500 feet (2,000 m)
Derate maximum operating temperature by
1 °C per 1,000 feet (300 m) for operation
between 5,000 feet (1500 m) and 6,500 feet
(2,000 m)
Storage Altitude Up to 50,000 feet (15 000 m)
Installation Category
II
Pollution Degree 2
Front Panel Voltage and Current
Control
10-turn voltage and current potentiometers
Front Panel Voltage Control Resolution 0.02% of maximum voltage
Front Panel Current Control Resolution 0.02% of maximum current
Front Panel Voltage and Current
Meters
3-digit green numeric LED displays. For
meter accuracy, see Table 1.3, on page 18
AC Input Connector Type IEC 320 connector, appropriate power cord
provided for destination country
Input Fuses Non-user accessible, both lines fused.
Output Connector Front panel: 5-way binding posts maximum
current limit 30 A
Rear panel: 7.5–18 V models: bus bars with
0.3” holes. 33–120 V models: wire clamp
connectors
Sense Connector 5 terminal wire clamp connector
Analog Programming Connector 15-pin female DSUB connector
Chassis Ground Front panel binding post; chassis is
grounded through power cord
Cooling Fan cooled. Variable speed fan. Air flows
from front to rear, with vents on top, bottom,
and sides