22 ADAM-4550 User's Manual
4.2 Read Configuration
Description Requests to read the current
baud rate and address from the
module.
Syntax $AA2(cr)
AA: module address ( 2 hexa-
decimal characters )
Response !AATTCCFFPP(cr) if the com-
mand is valid (refer to “Set New
Configuration” in Command Set)
?AA(cr) if an invalid command is
entered
Example Command : $0A2(cr)
Response:
!0A40AA2103(cr)
4.3 Write Identification
Description Requests to assign identification
data to the module at address
AA. The identification character
lengths can range from 0 to 16
bytes including carriage-return.
Syntax $AA6(identification
characters)(cr)
Response !AA(cr) if the command is valid
?AA(cr) if an invalid command is
entered
Example Command:
$0A6ADAM4550 Unit#1(cr)
Response: !0A(cr)