Advantech 5000 Series Network Card User Manual


 
Command Set
5017/5018
Analog Input
$aaSiER
Name Initialize EEPROM data
Description Initializes all EEPROM data in a specified analog input
module to their default values. This command is sent
following a failed attempt to calibrate a module (the
module shows no effect from an attempted calibration).
Following initialization, the problem module should
readily accept calibration.
Syntax $aaSiER(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
address of the ADAM-5000 system.
Si identifies the I/O slot for which you wish to initialize
all EEPROM data.
ER is Initialize all EEPROM data command.
(cr) is the terminating character, carriage return (0Dh)
Response !aa(cr) if the command is valid.
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error
or communication error or if the specified address does
not exist.
! delimiter character indicating a valid command was
received.
? delimiter character indicating the command was
invalid.
aa (range 00-FF) represents the 2-character hexadecimal
address of an ADAM-5000 system.
(cr) is the terminating character, carriage return (0Dh)
6-50 ADAM-5000