Command Set
Analog Input Alarm
5013/5017/5017H/5017UH/5018/5018P
$aaSiCjAhs
Name Set Alarm Mode
Description Sets the High/Low alarm of the specified input channel
in the addressed ADAM-5000 system to either Latching
or Momentary mode.
Syntax $aaSiCjAhs(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
address of anADAM-5000 system.
SiCj identifies the desired slot i (i : 0 to 3) and the
desired channel j (j : 0 to 7).
Ahs is the Set Alarm Mode command.
h indicates alarm type and can have the value H = High
alarm, L = Low alarm
s indicates alarm mode and can have the value M =
Momentary mode, L = Latching mode
(cr) represents terminating character, carriage return
(0Dh)
Response !aa(cr) if the command was valid
There is no response if the system detects a syntax error
or communication error or if the specified address does
not exist.
! delimiter character indicating a valid command was
received.
aa represents the 2-character hexadecimal address of the
corresponding ADAM-5000 system.
(cr) represents terminating character, carriage return
(0Dh)
6-72 ADAM-5000