AEG 10000 Power Supply User Manual


 
15
Max. site altitude up to 1000m at rated power;
if the UPS is used above than
1000m, decreasing as follows:
Colour Blackline
Weight:
PROTECT C. 6000 90 kg
PROTECT C. 6000 S 35 kg
PROTECT C. 6000 BP 65 kg
PROTECT C.
10000 93 kg
PROTECT C.
10000 S 38 kg
PROTECT C.
10000 BP 68 kg
Dimension W x H x D:
PROTECT C. 6000 (S
/ BP) 260 mm x 717 mm x 570 mm
PROTECT C. 10000 (S
/ BP) 260 mm x 717 mm x 570 mm
Guidelines
The PROTECT C. complies with the product norm EN 50091.
The CE symbol on the unit certifies the compliance to the EG
guidelines for 73/23 EEC low voltage and for 89/336 EEC
electromagnetic compatibility (EMC), when following the
installation instructions in the manual.
For the 73/23 EEC low voltage guidelines
Reference number EN 62040-1-1 : 2003
For 89/336-EMV guidelines
Reference number EN 50091-2 : 1995
EN 61000-3-2 : 1995
EN 61000-3-3 : 1995
i
Warning:
This is a UPS product for restricted sales for
users only with appropriate knowledge. To avoid
interference, restrictions according installation
or additional measures may be required.
Altitude (m) 1000 1500 2000 2500 3000
Power 100% 95% 90% 85% 80%