AEG 10000 Power Supply User Manual


 
30
5.2.2 Connection diameter and protection
Please gather the minimal dimensions from the following
table:
Type PROTECT
C. 6000 (S) C. 10000 (S)
Diameter
Mains line
Loads connector
6 mm
2
6 mm
2
10 mm
2
10 mm
2
Protection
Mains fuse
32 A
50 A
Table 1: Connection diameter and protection
5.3 One phase mains connector
5.3.1 Preparation for the one phase mains connector
Before starting the connection tasks check that:
the values of the mains voltage (input voltage) and
frequency complies with the values on the label on the
UPS,
the grounding connection complies with the IEC norms
or with the regional regulations,
the UPS is connected to the mains via a separate and
fused line in a preswitched NS distribution,
the prefuse or the power fuse in the NS distribution has
the same or higher value as indicated on the label on
the rear of the UPS appliance,
the connection line from the prefuse to the UPS has to
have a minimal diameter as defined in table 1:
„Connection diameter and protection“
The UPS carries high voltage. The unit may only
be installed or opened by trained and qualified
personnel. Repairs may only be carried out by
qualified customer service staff!