American Power Conversion 208VAC Power Supply User Manual


 
5
Automatic Self-
Test
The UPS performs a self-test automatically when turned on, and every two
weeks thereafter (by default).
During the self-test, the UPS briefly operates the connected equipment on bat-
tery.
If the UPS fails the self-test, the replace battery LED
illuminates and im-
mediately returns to online operation. The connected equipment is not affected
by a failed test. Recharge the battery for 24 hours and perform another self-test.
If it fails, the battery must be replaced.
Manual Self-Test
Press and hold the button for a few seconds to initiate the self-test.
C
IRCUIT BREAKERS (208V MODELS ONLY)
Input Circuit Breaker
One 40 Amp input circuit breaker is provided to the right of the
rear connector plug and to the left of the battery pack connector.
Output Circuit Breakers
Two output circuit breakers are provided.
On Battery Operation
The Smart-UPS switches to battery operation automatically if the utility power fails. While running
on battery, an alarm beeps four times every 30 seconds.
Press the
button to silence the UPS alarm (for the current alarm only). If the utility power does
not return, the UPS continues to supply power to the connected equipment until the battery is ex-
hausted.
If PowerChute is not being used you must manually save your files and power down before the UPS
turns off.
D
ETERMINING ON BATTERY RUN TIME
UPS battery life differs based on usage and environment. It is recommended that the battery/batteries
be changed once every three years. See the APC web site, www.apc.com
, for on battery run times.
Optional External Battery Pack(s)
To connect an optional external battery pack(s), refer to the 3U Rack Mount External Battery Pack
User’s Manual.