American Power Conversion 208VAC Power Supply User Manual


 
6
3: USER CONFIGURABLE ITEMS
NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE OR OPTIONAL SMART SLOT
ACCESSORY CARDS.
FUNCTION
F
ACTORY
DEFAULT
USER SELECTABLE
CHOICES
D
ESCRIPTION
Automatic Self-Test Every 14 days
(336 hours)
Every 7 days
(168 hours),
On Startup Only, No
Self-Test
This function sets the interval
at which the UPS will execute
a self-test. Refer to your soft-
ware manual for details.
UPS ID UPS_IDEN Up to eight characters to
define the UPS
Use this field to uniquely
identify the UPS, (ie. server
name or location) for network
management purposes.
Date of Last Battery Re-
placement
Manufacture
Date
Date of Battery Replace-
ment
mm/dd/yy
Reset this date when you
replace the battery module.
Minimum Capacity Before
Return from Shutdown
0 percent 15, 50, 90 percent The UPS will charge its bat-
teries to the specified percent-
age.
Voltage Sensitivity
The UPS detects and reacts
to line voltage distortions
by transferring to battery
operation to protect the
connected equipment.
Where power quality is
poor, the UPS may fre-
quently transfer to battery
operation. If the connected
equipment can operate
normally under such condi-
tions, reduce the sensitivity
setting to conserve battery
capacity and service life.
Brightly lit: UPS is set to
high sensitivity (default).
Dimly lit: UPS is set to
medium sensitivity.
Off: Low battery
warning interval is about
eight minutes.
To change the UPS sensitiv-
ity, press the voltage sensitiv-
ity button
(rear panel).
Use a pointed object (such as
a pen) to do so.
You can change the sensitiv-
ity level through PowerChute
software.
Alarm Delay
After Line Fail
5 second delay 30 second delay,
At Low Battery
Condition,
No Alarm
Set alarm delay to avoid
alarms for minor power
glitches.
Shutdown Delay 20 seconds 180, 300, 600 seconds Sets the interval between the
time when the UPS receives a
shutdown command and ac-
tual shutdown.