American Power Conversion 240-320kW 400V Power Supply User Manual


 
70 Installation Guide APC Silcon 240-320kW 400V UPS
990-4045a
System Specifications
7.0 System Specifications
7.1 Technical Data
7.2 Dimensions / Weight
Voltage 3x380/400/415V
Input Voltage tolerance
Normal operation
Bypass operation
+
15%
+
10% (standard)
+
4, 6, 8% (programmable)
Frequency 50Hz/60Hz
+
6 standard
+
0.5-8% (programmable)
Input power factor load 25% minimum 0.97
load 100% minimum 0.99
Current distortion Max. 5%
Output Voltage 3x380/400/415V
Voltage tolerance +
1% static symmetrical load
+
3% static symmetrical load
+
5% 0-100% load step
Voltage distortion max. 3% linear load
max. 6% non-linear load
Load power factor 0.9 lead to 0.8 lag
Frequency 50Hz/60Hz (mains synchronized)
+
0.1% free-running
Overload capacity
Mains operation
Mains operation
Battery operation
Bypass operation
200% - 60 seconds
125% - 10 minutes
150% - 30 seconds
125% - continuous
General Ambient temperature 0-40
o
C (Temperatures above 25
o
C will
reduce battery lifetime)
Humidity
Protection class
Safety
Emission and Immunity
Static bypass switch
Auto restart
Economy mode
Max. 95% non-condensing
IP30
EN 50091-1
CE Mark
EN 50091-2
Built-in
Programmable
Programmable
Type 240kW 320kW
Height [mm] 1800 1800
Width [mm] 1600 1600
Depth [mm] 800 800
Weight [kg] 1400 1400