American Power Conversion 240-320kW 400V Power Supply User Manual


 
72 Installation Guide APC Silcon 240-320kW 400V UPS
990-4045a
Appendix
9.0 Appendix
9.1 Table 1. Installation Planning Data
Main Input
Breaker
Field
Wiring*
Battery Bank**
UPS Module
Service Bypass Panel
Field
Wiring
Output
Breaker
*
** Internal Batteries available for 40kW units and smaller
*
*
Q1
Q2
Q3
* Not supplied by APC
Installation Planning Data
APC Silcon Series
AC Input Battery System DC AC Output
Min. Input Input Full I
Nom
I
Max
Load side Heat
Power rating Source P (kW) I (A) Cable Overcurrent V
n
load Disch Disch I
n
Overcurrent Dissipation
kW kVA Pf V Hz Nom. Max. Nom. Max. (per phase) Protection* (Vdc) P(kW) (A) (A) (A) Protection* (kW)
240 240 1 380
400
415
50/60 256.6 307.5 421.7
403.5
386.6
463.9
443.8
425.3
2//120mm
2
500 A 2x384 252.7 329 388 363.6
347.8
333.3
400 A 9.2
320 320 1 380
400
415
50/60 333.9 407.4 558.8
507.3
512.3
614.7
588.0
563.5
2//185mm
2
630 A 2x384 334.8 436 514 484.8
463.8
444.4
500 A 10.6
COLUMN 1a 1b 1c 1d 1e 1f 1g 1h 2a 2b 2c 2d 3a 3b 4a
NOTES 3 4 1 2 9 5, 6, 13 8 12 10 11 6, 7 13
* Provided by others