American Power Conversion 5000 VA Power Supply User Manual


 
8
USER CONFIGURABLE ITEMS
NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE, OPTIONAL SMART SLOT
ACCESSORY CARDS, OR TERMINAL MODE.
FUNCTION
F
ACTORY
DEFAULT
USER SELECTABLE
CHOICES
D
ESCRIPTION
Automatic Self-Test On start-up and
every 14 days,
thereafter
On start-up and every 7
days thereafter
On start-up and every 14
days thereafter
On start-up only
No self-test
Set the interval at which the
UPS will execute a self-test.
Date of Last Battery
Replacement
Manufacture date Date of
battery replacement
Reset this date when you replace
the battery modules.
Minimum Run time
Before Return from
Shutdown
0 seconds 0 to 3600 s of run time
Specify the minimum run time
following a low battery
shutdown, before powering
connected equipment.
Audible Alarm
Setting
ON ON, OFF Enable or disable all alarms
permanently.
Simple Shutdown
Delay
90 seconds 0 to 1800 s Set the interval between the time
when the UPS receives a simple
shutdown command and the
actual shutdown.
Simple Low Run
Time Warning
150 seconds 0 to 1800 s Change the warning interval
default to a higher setting if the
operating system requires a
longer interval for shutdown.
The low battery warning beeps
are continuous when 150
seconds of run time remain.
High Bypass Point
255 VAC
Output Voltage Setting
200 VAC:
210 - 280 VAC
208 VAC:
220 - 280 VAC
220 VAC:
235 - 280 VAC
230 VAC:
245 - 280 VAC
240 VAC:
255 - 280 VAC
Maximum voltage that the UPS
will pass to connected
equipment during internal
bypass operation.