American Power Conversion 5000 VA Power Supply User Manual


 
9
NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE, OPTIONAL SMART SLOT
ACCESSORY CARDS, OR TERMINAL MODE.
FUNCTION
F
ACTORY
DEFAULT
USER SELECTABLE
CHOICES
D
ESCRIPTION
Low Bypass Point
160 VAC
Output Voltage Setting
200 VAC:
160 - 185 VAC
208 VAC:
160 - 190 VAC
220 VAC:
160 - 195 VAC
230 VAC:
160 - 200 VAC
240 VAC:
160 - 205 VAC
Minimum voltage that the UPS
will pass to connected
equipment during internal
bypass operation.
Output Voltage XLJ models:
200 VAC
XLT models:
208 VAC
XLTW models:
220 VAC
XLI models:
230 VAC
200, 208, 220,
230, 240 VAC
Allows the user to select the on
on-line output voltage.
50 ± 3 Hz
50 ± 1 Hz
50 ± 0.1 Hz
60 ± 3 Hz
60 ± 1 Hz
60 ± 0.1 Hz
Output Frequency Automatic
50 ± 3 Hz or
60 ± 3 Hz
50 ± 3 Hz or 60 ± 3 Hz
Sets the allowable UPS output
frequency. Whenever possible,
the output frequency tracks the
input frequency.
Number of External
Battery Packs
0 0 to 100 Defines the number of external
connected battery packs for
proper run time prediction.
Bypass Acceptable Not required Required/ Not required Phase and frequency lock
required/not required before the
UPS will switch to bypass.