American Power Conversion MXA002 Power Supply User Manual


 
Page 9
Diagram showing power distribution plate earth connection
3.0 Installation
3.4 Output wiring procedure - continued
3.4.4 Use a 3/8" wrench to remove the protective earth wire (green with yellow stripes) ring
terminal fastened at the earthing stud on the Isolation Unit.
3.4.5 Remove the desired knock-out from the new power distribution plate. See the Input
wiring procedure, section 3.3, for instructions on how to remove the knock-out.
3.4.6 Fasten an appropriately sized and approved cable clamp (not provided) onto the power
distribution plate.
3.4.7 Strip insulation from the output cable wire ends at the length given in Table 3.2.1.
3.4.8 Thread the output cable through the cable clamp and through the power distribution plate
hole. Arrange the cable so that the end is near the output termination block.