American Power Conversion MXA002 Power Supply User Manual


 
Page 11
3.0 Installation
3.4 Output wiring procedure - continued
Figure 3.4.1
1f, 208 Vac loads only
3000 VA model with MXA002 hard-
wire kit: 15 Amp maximum.
5000 VA model with MXA001 hard-
wire kit: 24 Amp maximum.
Figure 3.4.2
1f, 240 Vac loads only
3000 VA model with MXA002 hard-
wire kit: 12.5 Amp maximum.
5000 VA model with MXA001 hard-
wire kit: 21 Amp maximum.
Figure 3.4.3
1f, 120 Vac loads only
3000 VA model with MXA002 hard-
wire kit: 25 Amp maximum.
5000 VA model with MXA001 hard-
wire kit: 30 Amp maximum.
Figure 3.4.4
1f, 120 Vac loads only
3000 VA model with MXA002 hard-
wire kit: 25 Amp maximum.
5000 VA model with MXA001 hard-
wire kit: 30 Amp maximum.
(Alternate of connection scheme
shown in Figure 3.4.3.)