APC Redundant Switch: Installation and Operation Manual 19
Troubleshooting
Troubleshooting
communications
and lost
redundancy
With the high availability system, the attached
UPS
s are polled
continuously for capability to carry a load and ability to
communicate with the management software (PowerChute
plus
). When a problem with one of the
UPS
s occurs, power to
the load is not interrupted and polling continues, and
PowerChute
plus
responds by displaying the message, “Self
test failed: invalid test.”
Communications Problems.
If the message “Self test failed:
invalid test.” occurs repeatedly:
1. Check the communications path between the
UPS
s and
the Redundant Switch.
2. Check the front panel of the Redundant Switch.
If the Status Select
LED
s are flashing in any sequence,
the Redundant Switch has failed. See “Basic
troubleshooting” on page 18.
If the front panel appears normal, there may be a
UPS
or server communications problem, See the
troubleshooting and service sections of your
UPS
manuals.
If you need more help, contact
APC
Worldwide
Customer Support.
Loss of Redundancy.
If the Redundant Switch
LED
for
UPS
-
B
is off,
UPS
-
B
has lost the ability to provide power to the
equipment load when engaged. If the
LED
for
UPS
-A is off,
UPS-A has failed, and power is now provided by
UPS
-
B
. See
the troubleshooting and service sections of your
UPS
manuals.
If PowerChute
plus
displays the message “self test failed:
invalid test” briefly or several times, the output voltage of
UPS
-
A
has dropped. Perform a
UPS
self-test through
PowerChute
plus
.
If the self test fails, see the troubleshooting and service
sections of your
UPS
manuals.
If you need more help, contact
APC
Worldwide
Customer Support.