American Power Conversion SYTF2J Power Supply User Manual


 
CHAPTER 4: SPECIFICATIONS
12
Product Specifications
Electrical Specifications
AP9621 / SUTF3 / SYTF2 /
SYTF3 / SURT005
SYTF2J / SYTF3J / SURT006
Nominal Input Voltage (VAC) 208 200
Input Voltage Range (VAC) 185 to 230* 180 to 220
Maximum Input Current (amps)
Line cord Installation (L6-30)
Hardwire Installation
24
26**
22
Line Frequency (Hz) 60 50 or 60
Efficiency 90 to 95%
Nominal Output Voltage (VAC) 120 100
Maximum Output Power (VA)
Line cord Installation (L6-30)
Hardwire Installation
4500*
5000*
3500
3500
* For continuous operation below Vin = 205 VAC, the output load must be reduced to limit the maximum input
current to the amount specified in the table above. Continuous operation above the maximum specified input
current may cause the unit to overheat and shutdown. Please contact APC for additional information.