AMX NXA-UPS1500 Power Supply User Manual


 
NXA-UPS1500 Uninterruptible Power Supply
2
NXA-UPS1500 Uninterruptible Power Supply
Product Specifications
NXA-UPS1500 Product Specifications
Input: Voltage Window (DIP Switch selectable):
120V version (FG678-15): 110/115/120 Vac +35% ˜ -32%
240V version (FG678-20): 220/230/240 Vac +35% ˜ -32%
Frequency: 45 ˜ 65Hz (50/60Hz auto-sensing)
Output: Voltage Window (AC Mode):
120V version (FG678-15): 110/115/120 Vac +8% ˜ -12%
240V version (FG678-20): 220/230/240 Vac +8% ˜ -12%
Voltage Window (INV Mode):
120V version (FG678-15): 110/115/120 Vac +/-5%
240V version (FG678-20): 220/230/240 Vac +/-5%
Capacity (VA/W):1500/900
Wave Form: Pure sine wave
Frequency: 50Hz/60Hz +/-0.1Hz
Transfer Time:2 ms typical
Autonomy: > 8 min.
DC Start: Yes
Battery: Type: 12V, sealed lead acid maintenance-free
Capacity: 9AH
Quantity: 4 12V batteries required
Voltage:
120V version (FG678-15): 24 Vdc
240V version (FG678-20): 48 Vdc
Recharge Time: 2 ˜ 4 hours to 90%
Storage: Store at -15 to +30 °C (+5 to +86 °F), charge the UPS battery every 6
months / Store at +30 to +45 °C (+86 to +113 °F), charge the UPS battery every
3 months.
LED indicators: Utility mode
Backup mode
Battery conditions
Display LCD: Load level (%)
Battery level (%)
Bypass
AVR-Boost/AVR Buck
Battery Low/Replace/Fault
•UPS Fault
Site Wiring Fault
Overload
Overload Protection: AC Mode: >110% Buzzer continuously alarms, and shuts down in 10 minutes.
Inverter Mode: >120% Buzzer continuously alarms, and shuts down in 10
seconds.
Short Circuit Protection: AC Mode: Breaker and electronic circuit
Inverter Mode: Shut down automatically in 8 cycles
Self-Diagnostics: Upon Power-on
Alarms: Line Failure
Battery Low
Overload and Fault
Operation Environment: Temperature: 32° - 104°F (0-40° C)
Operation Humidity: 95% RH Maximum, non-condensing