APC 1400XLT Power Supply User Manual


 
990-7031D, Revision 5 5/01
10
The SmartTrim LED comes on to indicate that the UPS is compensating for a high voltage.
SmartBoost
The SmartBoost LED comes on to indicate that the UPS is compensating for a low voltage.
Low Battery
When the UPS is operating on-battery and the energy reserve of the battery runs low, the UPS beeps continuously until
the UPS shuts down from battery exhaustion or returns to on-line operation.
Cold Start
When the UPS is off and there is no utility power, use the cold start feature to apply power to the loads from the UPS’s
battery.
Note:
Cold start is not a normal condition.
Press and hold the on/test button until the UPS beeps.
Release the on/test button during the beep and the loads are powered within four seconds.
The display indicates that the voltage is between the displayed value from the list and the next higher value. For example,
with three LEDs lit, the input voltage is between 208 and 223 VAC.
If no LEDs come on and the UPS is plugged into a working AC power outlet, the line voltage is extremely low.
If all five LEDs come on, the line voltage is extremely high and should be checked by an electrician.
Note:
The UPS starts a self-test as a part of this procedure. The self-test does not affect the voltage display. The utility voltage
bar graph has a margin of error of ± 4%.
239
223
208
193
177
Utility Voltage Bar Graph
This UPS has a diagnostic feature that displays the utility voltage. With the UPS plugged into the normal utility
power, press and hold the on/test button to see the utility voltage bar graph display. After approximately four
seconds the 5-LED display on the right of the front panel shows the utility input voltage. Refer to the figure to the
left for the voltage reading (values are not listed on the UPS).