APC 1400XLT Power Supply User Manual


 
990-7031D, Revision 5 5/01
19
Specifications
1400 VA 2200 VA 3000 VA 5000 VA
Acceptable input voltage 0 - 325 VAC
Input voltage (on-line operation)* 160 - 253 VAC
208 volt output range* 177 - 229 VAC
120 volt output range *
with 400 VA load
with no load
95 - 130 VAC
100 - 135 VAC
Nominal input frequency 50 or 60 Hz, autosensing
Input protection Resettable circuit breaker
Frequency limits (on-line operation) 47 to 63 Hz
Transfer time 2 ms typical, 4.5 ms maximum
Maximum load, total 1400 VA/950 W 2200 VA/1600 W 3000 VA/2250 W 5000 VA/3750 W
Maximum load, 120V auxiliary 400 VA/400 W
On-battery output voltage 208 VAC
On-battery frequency 50 or 60 Hz, ñ0.1 Hz;
unless synchronized to utility during brownout
On-battery waveshape Low-distortion sine wave
Overload protection (on-battery) Overcurrent and short-circuit protected, latching shutdown on overload
Overload protection (on-line) 2 pole, 20 Amp UL certified input circuit breaker
Overload protection
(120 VAC auxiliary)
Transformer and output protected by resettable
thermal circuit breaker (on-line and on-battery)
Surge energy rating
(one time, 10/1000 æs waveform)
1120 J
Surge current capability
(one time, 8/20 æs waveform)
6500 A maximum
Surge response time 0 ns (instantaneous) normal mode;
<5 ns common mode
Surge voltage let-through
(percentage of applied ANSI C62.41 Cat. A
ñ6 kV test waveform)
0.30%
Noise filter Normal and common mode EMI/RFI suppression,
100 kHz to 10 MHz
Battery type Spill proof, maintenance free, sealed lead-acid
Typical battery life 3 to 6 years, depending on number of discharge cycles
and ambient temperature
Typical recharge time 2 to 5 hours from total discharge
Operating temperature 0 to 40§C (+32 to +104§F)
Storage temperature -15 to +45§C (+5 to +113§F)
Operating and storage relative humidity 5 to 95%, non-condensing
Operating elevation 0 to +3,000 m (0 to +10,000 ft.)
Storage elevation 0 to +15,000 m (0 to +50,000 ft.)
Electromagnetic immunity IEC 801-2 level IV, 801-3 level III, 801-4 level IV
Audible noise in dBA at 1 m (3 ft.) <55
Safety approvals Listed to UL 1778, certified to CSA 107.1
EMI verification FCC/DOC Class A verified
5U Units RM Units
Size (W x H x D)
43.2 x 19.6 x 54.6 cm
(17.0 x 8.7 x 21.5 in.)
43.2 x 19.6 x 62.2 cm
(17.0 x 8.7 x 24.5 in.)
Weight - net (shipping) 120 (143) lb.
54.3 (64.8) kg
137 (160) lb.
62.0 (72.5) kg
137 (160) lb.
62.0 (72.5) kg
225 (245) lb.
102 (111) kg
3U Units Tower Units
Size (W x H x D) 43.2 x 13.3 x 62.2 cm
(17.0 x 5.25 x 24.5 in.)
19.6 x 43.2 x 62.2 cm
(8.7 x 17.5 x 26.0 in.)
Weight - net (shipping)
128 (148) lb.
58 (67) kg
230 (250) lb.
105 (114) kg