APC DP300E Series Power Supply User Manual


 
19User Guide Silcon DP300E Series 480V 400-500kVA
7OA0004 US rev. 02
Programming Parameters
4.3.2 Programming example – change charge voltage to 446V*
Action Display shows
1. Press
and simultaneously to open
for password input
2. Enter password xx xx xx by pressing
3. Press
or until
4. Press
5. Press to store
6. Wait about 1 second
7. Press
to exit
4.3.3 Programming example - change to output isolation transformer
present**
Action Display shows
1. Press and simultaneously to open
for password input
2. Enter password xx xx xx by pressing
3. Press
or until
4. Press
for change
5. Press
to store
6. Wait about 1 second
7. Press
to exit
Last selected
parameter
Boost charge voltage
: 438
Boost charge voltage
: 446
Data stored
Boost charge voltage
: 446
Normal operation
load power XX%
Key in password
:
Key in password
:
Last selected
parameter
Normal operation
load power XX%
Isolation trafo output
: YES
Data stored
Isolation trafo output
: NO
Isolation trafo output
: YES
** The other parameters are
selected by pressing the
key
as step 4 in example 4.3.3. -
one or more times.
NOTE:
Only for APC personnel and
certified local APC personnel.
* For charge voltages, battery
warnings and shut down
voltages, and high battery
temperature, the parameter is
changed by entering the actual
value like example 4.3.2.